STUDI EKSPERIMEN PENGARUH POROSITY RATIO PADA PERFORATED TWISTED TAPE INSERT TERHADAP KARAKTERISTIK HEAT TRANSFER DAN FRICTION FACTOR PADA PENUKAR KALOR PIPA GANDA

Authors

  • Susi Puspitasari Politeknik Elektronika Negeri Surabaya
  • Arrad Ghani Safitra Politeknik Elektronika Negeri Surabaya

DOI:

https://doi.org/10.34151/technoscientia.v11i2.806

Keywords:

Heat transfer, friction factor, double pipe heat exchanger, perforated twisted tape

Abstract

Heat exchanger is used device to transfer thermal energy (enthalpy) between two or more fluids at different temperatures. One type of heat exchanger is double pipe heat exchanger. Double pipe heat exchanger consists of one pipe placed concentrically in another pipe with a larger diameter. One fluid passes through the inner pipe and the other fluid passes through the outer pipe (annulus). Performance of double pipe heat exchangers can be determined based on the characteristics of heat transfer and friction factor. One effort to improve the performance of double pipe heat exchanger can by passive method which is adding perforated twisted tape in the inner pipe. Perforated twisted tape had three different porosity ratios, that is 1.88, 3.77, and 5.65% that comparison with plain twisted tape (porosity ratio 0). Fluid flowed in double pipe heat exchanger is water in liquid phase in laminar-transition flow regime. Reynolds number in annulus is made constant at 2000, while in inner pipe is 1000-5000. Temperature of water entering annulus and inner pipe is kept constant at 20ºC and 50ºC, respectively. From the experimental results it found that perforated twisted tape increased Nusselt number and friction factor values respectively 0.1-0.8% and 203-1536% higher than double pipe heat exchanger without twisted tape (plain tube). Perforated twisted tape with porosity ratio 3.77% has the best performance, that is increasing Nusselt number average of 0.31% from 28.8913 in plain tube to 28.9810 and increasing friction factor average of 366.34% from 0.6521 in plain tube to 3.0410.

References

Bhuiya, M., Chowdhury, M., M.Saha, & Islam, M., 2013, Heat transfer and friction factor characteristics in turbulent flow through a tube fitted with perforated twisted tape insert. International Communications in Heat and Mass Transfer, vol. 46, pp. 49-57.
Cengel, Y. A., 2005, Heat Transfer A Pratical Approach (2nd ed.).
Eiamsa-ard, S., Wongcharee, K., Sripattanapipat, S., 2009, 3-D Numerical simulation of swirling flow and convective heat transfer in a circular tube induced by means of loose-fit twisted tape. International Communications in Heat and Mass Transfer, vol. 36, pp. 947-955.
Incopera, F. P., Dewitt, D. P., 2011, Fundamentals of Heat and Mass Transfer (7th ed.), United Sates of America: John Wiley & Sons.
Kakac, S., Liu, H., 2002, Heat Exchanger Selection, Rating and Thermal Design (2nd ed.), Florida: CRC Press LLC.
Kumar, C. N., Murugesan, P., 2012, April). Review on Twisted Tapes Heat Transfer Enhancement. International Journal of Scientific & Engineering Research, vol. 3, pp. 1-9.
Naphon, P., 2006, Heat transfer and pressure drop in the horizontal double pipes with and without twisted tape insert. International Communications in Heat and Mass Transfer, vol. 33, pp. 166-175.
Sarada, S. N., Raju, A. S., Radha, K. K., & Sunder, L. S., 2010, Enhancement of heat transfer using varying width twisted tape insert. International Journal of Engineering Science and Technology, vol. 2, pp. 107-118.
Serth, R. W., 2007, Process Heat Transfer Principles and Applications. United Kingdom: Elsevier.
Shah, R. K., Sakulic, D. P., 2003, Fundamental of Heat Exchanger Design. New Jersey: John Wiley & Sons, Inc.

Downloads

Published

01-02-2019

How to Cite

Puspitasari, S., & Safitra, A. G. (2019). STUDI EKSPERIMEN PENGARUH POROSITY RATIO PADA PERFORATED TWISTED TAPE INSERT TERHADAP KARAKTERISTIK HEAT TRANSFER DAN FRICTION FACTOR PADA PENUKAR KALOR PIPA GANDA. JURNAL TEKNOLOGI TECHNOSCIENTIA, 11(2), 121–127. https://doi.org/10.34151/technoscientia.v11i2.806