KARAKTERISTIK MENARA PENDINGIN DENGAN BAHAN ISIAN TALI IJUK

Authors

  • Susanto Johanes Jurusan Teknik Mesin, Universitas Gadjah Mada, Yogyakarta

DOI:

https://doi.org/10.34151/technoscientia.v4i1.494

Keywords:

Cooling tower, characteristic, effectiveness, palm-fibre ropes

Abstract

In this study the characteristics of a water cooling tower with palm fibre as the packing  material have been investigated experimentally. The experiments were carried out in a rectangle glass tower of 81 cm2 cross sectional area and 100 cm height. The packing used was constructed of 8 palm-fibre ropes (of about 0,6 cm diameter), zigzag and cross of water flow, and then it  placed above the stainless steel support on the tower bottom. There were two type of packing i.e. 21,7.10-4 and 28,3.10-4 kg weigh of rope every m3 volume of the  packing. The experimental results show that the increasing of the  water inlet temperature and packing height causes the increasing of the tower characteristic . Mean while the increasing of the  water/air mass flow rate ratio causes the decreasing of the tower characteristic.The tower characteristics is as a function of the investigated variables which expressed as: NTU = 165,24.10-3 (mw/ma)-0,999 (Z)0,5343 (Twi)0,1429  It is  for 21,7.10-4 kg/m3 of the specification of the packing material,  with the relative error of 6,1 %, and     NTU = 3,35.10-3 (mw/ma)-0,995 (Z)0,5050 (Twi)1,1643. It is  for 28,3.10-4 kg/m3 of the specification of the packing material,  with the relative error of  5,5 %.These equations are valid for the range variables, they are  mw/ma of 4,46 – 9,48, Z of 30 – 90 cm, Twi of 50 – 60 oC.   The mean effectiveness of the heat transfer were calculated to be  24,8 % and 25,9 %, respectivally for 21,7.10-4 and 28,3.10-4 kg/m3 of the specifications of the packing material.

References

Arora, C P., 1986, Refrigeration and Air
Conditioning, 3th ed., Tata Mcgraw-Hill Publishing Company Limited, New Delhi.
El-Dessouky, H., 1993, Thermal and
Hydraulic Performance of a Three-Phase Fluidized Cooling tower, Thermal Experimental and Fluid Science, 6, 417-426.
Haar, L., Gallagher, J.S., dan Kell, G.S.,
1984, NBS/NRC Steam Tables, The United States Secretary of Commerce, USA.
Jamilah, S., 1999, Unjuk Kerja Menara Pendingin dengan Plat Aluminium Sebagai Pendistribusi Aliran, Laporan Penelitian Laboratorium Teknologi Kimia Umum, Fakultas Teknik, Universitas Gadjah Mada, Yogyakarta.
Prayitno, 1993, Karakteristik Susunan Bilah Pengisi yang Menggunakan Permukaan Bergelombang pada Menara Pendingin dengan Aliran Lawan Arah, Laporan Penelitian DPP-UGM 1992/1993, Fakultas Teknik Universitas Gadjah Mada, Yogyakarta.
Mulyono dan Baskoro, 2000, Karakteristik Menara Pendingin Dengan Bahan Isian Plastik Bergelombang, Media Teknik, No.1, Tahun XXII, Edisi Februari.
Ramli, 1998, Karakteristik Menara Pendingin dengan Plat Sebagai Pendistribusi Cairan, Laporan Penelitian Laboratorium Teknologi Kimia Umum, Fakultas Teknik, Universitas Gadjah Mada, Yogyakarta.
Stoecker , Jones, 1987, Refrigerasi dan Pengkondisian.

Downloads

Published

18-01-2019

How to Cite

Johanes, S. (2019). KARAKTERISTIK MENARA PENDINGIN DENGAN BAHAN ISIAN TALI IJUK. JURNAL TEKNOLOGI TECHNOSCIENTIA, 4(1), 103–112. https://doi.org/10.34151/technoscientia.v4i1.494